BC360 Specifications
BC360 - Power Supply and Battery charger
Specifications
Electrical data at 50Hz input voltage:
Input voltage
Input current at nominal load
Power Factor (PF)
Efficiency at full load
Nominal output voltage
Nominal output current
Load sharing
Output voltage ripple and noise
Output voltage regulation
Adjustable current limit
Max input current
Rated input current
Total Harmonic Distortion (THD)
Short circuit current 99 - 264VAC
7,3 A at 230VAC
> 0,95 (typical 0.99 )
>85% @115VAC
>87% @230VAC
28VDC (adjustable 20 - 31VDC)
50A
Better then 10% deviation with 2 - 10 units in parallel
<120mV p-p, 20 MHz bandwidth
±0,5% zero/max load
5 - 50A
17,1A @ 99VAC
14,6A @ 115VAC
<8% @ full load
<_58.OA
Input current at 400Hz input voltage:
Input current at max load
Input current at max load 15A@115V
8,5A@230V
Environmental
High temperature:
Operation
MIL-STD-810E: Method 501.3, Procedure II to 480C
Storage
MIL-STD-810E:Method 501.3, Category A1,hot induced, 710C
Low temperature:
Operation
MIL-STD-810E: Method 502.3, Procedure II, - 400C
Storage
MIL-STD-810E: Method 502.3, Procedure I, -510C
Temperature shock
MIL-STD-810E: Method 503.3, -510C - 48°C. (Non-operational)
Humidity
The power supply operates as specified when exposed to high humidity as per MIL-STD-810E, Method 507.3
Vibration
According to MIL-STD-810E. Method 514.4, cat. 8 (Ground Mobile), with level 514.4-1 (Basic Transportation)
Shock
MIL-STD-810E. Method 516.4, Procedure I, functional shock.
Fungus
Analysis of the degree of inertness to fungus growth of the components in accordance with MIL-HDBK454
Altitude
Designed to meet MIL-STD-810E: Method 500.3, Procedure I (Storage), II (Operational), and III (Rapid decompression), Test altitude is 4750 metres at 57.2K.a for all tests
EMC
TREE:
Designed to meet QSTAG 620 (Transient Radiation Effect on Electronics)
Electromagnetic Interference
The power supply meets the requirements of MILSTD-461D; Ground Army; CE101, CE102, RE102, RS103, CS101, CS114 and CS 116
Electromagnetic Pulse (EMP)
Designed to operate without fault after exposure to EMP levels defined in paragraph A5 of QSTAG 244, edition no 3, amendment no. 1, dated 6 June 1983
Electrostatic discharge
The power supply meets the requirements of MILSTD-1686 for ESD
Safety
EN 60950
Encapsulation
IP32 (front)
Cooling
Forced air b 2 seed controlled fans
Mechanical data
Dimensions W x D x H incl. handles
Weight
Cabinet 483x391x88 mm (2U)
11.5 kg
Standard 19 inch rack