BC360 Functions

BC360 - Power Supply and Battery charger

Functions:

  • Under voltage
    An alarm is given when the output voltage drops below 20V. The alarm disappears when the voltage rises higher than 21.5V.
  • Over voltage
    An alarm is activated if output voltage exceeds 32V.
  • Over temperature
    The unit is protected from over temperature.
  • Output circuit breaker
    If an output current higher than aprox. 70A occurs, a circuit breaker is released and rectifier is shut off. Alarm is given.
  • Input circuit breaker
    If an input current higher than 25A occurs, a circuit breaker is released and rectifier is shut off.
  • Alarms
    Alarm signals are fed to a common potential free output, and are indicated in separate LEDs for:
    • Power OK
    • Failure
    • Current limit
  • Input voltage When the input voltage decreases to a given level, the rectifier is shut off. When the voltage returns, the rectifier is turned on again.
  • Connectors AC: MS3102E16-10P DC: MS3102E22-2S Mon, Par/NTC and Par: Binder 09-0482-00-08
  • Grounding Available in front (M5)
  • Acoustic noise Max. 55 dBa @50 Hz
  • Frequency range 45 - 420Hz

Related links